Do Sepam 20/40/60/80 motor protection relays report starting time even if locked rotor/excessive starting time protection (ANSI code 48/51LR) is not activated?
In this FAQ, we explain how Sepam measure the starting time of a machine.
There is a difference when we enbale or disable locked rotor/excessive starting time protection.

AEDL3

Schneider Electric Sverige

Bilagor
FA301276.docx [47.03 KB]
Do Sepam 20/40/60/80 motor protection relays report starting time even if locked rotor/excessive starting time protection (ANSI code 48/51LR) is not activated?
In this FAQ, we explain how Sepam measure the starting time of a machine.
There is a difference when we enbale or disable locked rotor/excessive starting time protection.

AEDL3

Schneider Electric Sverige

Bilagor
FA301276.docx [47.03 KB]
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.